Online Monitoring Of Insulation Of Industrial Power Cables

Sep 20, 2026

Leave a message

A low-frequency AC signal is injected into the power cable supply system via a zero-sequence reactor L and a three-phase reactor SL, forming a low-frequency current loop with the cable's insulation resistance to ground and the earth. The current signal is acquired by a Hall effect zero-sequence current transformer, and then processed through a notch filter circuit, filtering, amplification, and rectification to extract the low-frequency current signal related to the cable insulation resistance. This signal is converted into a digital signal by an A/D converter, and finally analyzed and processed by a microcontroller to obtain the cable's insulation resistance to ground. The insulation parameter value is displayed in real time on an LCD screen, and an audible and visual alarm is triggered when the insulation resistance drops to a specified value.

 

The microprocessor used in this design is the AT89S52 microcontroller, a low-power, high-performance CMOS 8-bit microcontroller with 8k Flash memory. The main I/O interface circuits of the system include control buttons, an LCD screen, and an audible and visual alarm circuit for cable insulation faults. According to relevant coal mine safety regulations, alarm values ​​can be set or modified via buttons according to different voltage levels. When the insulation resistance falls below the set value, the circuit triggers an alarm. Conversely, if the situation is different, then no alarm will be triggered.